Lydall Affinity Chiller (CAA-007T-BE59CBN3) (AMS P/N: 0133-3510)

This is the embedded chiller from the AMS Greenlight HPS surgical laser system, also known as a Laserscope. This chiller, contained within the bottom section of the frame, maintains the temperature of the water loop that cools the laser diode stack, diode driver, and q-switch crystal baseplate. All of these components generate a significant amount of heat during operation, which is most efficiently removed using water cooling. The chiller uses a small condenser and fan to dump that heat into the ambient environment. Two heat exchangers are used to move heat from the laser's cooling water loop to the refrigerant, and then from the refrigerant to the ambient air. The chiller has a pre-programmed setpoint of around 77-79 degrees Fahrenheit for the water loop. It's not a deep cool chiller, and is only intended to maintain a suitable temperature for the sensitive components. In fact, it's more of a precision chiller as it has a heater for the water loop and a PID-controlled solid state relay output to fine tune the temperature (more on that further down). The chiller is controlled and monitored by its own dedicated controller along with the Greenlight HPS rear panel board over RS-485. The laser system turns on the chiller and constantly monitors its status, checks for alarms, and keeps an eye on the loop temperature. If the chiller malfunctions or the loop temperature falls too far out of range, the laser will shut down and display an error message related to the chiller. The laser will not enable if the chiller fails to start or is disconnected. Conveniently, the chiller can be easily removed from the Greenlight HPS frame after removing the electrical connections, quick disconnect water fittings, and two large bolts below the yellow fan shroud and filter cartridge.

Component overview

Lydall Chiller

The chiller weighs about as much as a medium-sized window air conditioner or portable A/C unit and can be removed and replaced as a module or serviced outside of the laser system. It's very compact and includes several critical components such as the compressor, condenser coil, condenser fan, water pump, sensors, water reservoir, and digital control board. According to the information label, it uses R-134A refrigerant.

Lydall Chiller

Components from left to right: Condenser coil assembly and filter, condenser fan (under yellow shroud), compressor and thermal expansion valve assembly, power supply and distribution, digital control board, water reservoir, and pump (under digital control board tray).

Lydall Chiller

On this side, the water pump and VFD (variable frequency drive) are visible. The pump and VFD are manufactured by Fluid-o-Tech. The pump is a TMFR1 integrated pump-motor unit, and is paired with a TMFE1 VFD. The pump is a high-reliability, magnetically-driven unit with no shaft seal to wear out or leak. The chiller board controls the AC input power to the VFD but only has the ability to turn it on or off. The VFD does have the capability for external speed control and monitoring, but that is not implemented on this system. It just runs the pump at a constant, pre-programmed speed as defined by the DIP switches.

Lydall Chiller

On the other side are multiple filters for the water loop which can be easily replaced using the CPC quick-disconnect fittings. Also visible is an inline flow switch which is constantly monitored by the control board. The controller will stop the pump if flow is not detected or if the reservoir level is too low, to prevent damage to the pump. Also installed are high and low pressure refrigerant sensors, which inform the controller of the status of the coolant loop. Buried deeper is an RTD (resistance temperature detector) which is used to accurately determine the temperature of the cooling water loop. Additionally, there is a heater connected to the loop, as mentioned earlier. The role of the heater is presumably to bring the temperature up in precise adjustments if the chiller overshoots, although our bench testing has raised some doubts about how it is controlled (more on that further down). According to the Greenlight HPS/XPS service manual, this chiller has a solenoid valve (lower left corner) that can be activated in order to allow return water to flow through a resin de-ionizing filter cartridge in order to keep the water resistivity around 0.25 megohm-cm. This is known as D.I. polishing. Presumably, this means there is also a sensor to determine the resistivity of the water, but we have not yet identified such a sensor. Based on our observations, the SPARE input is used to activate the D.I. polishing function, so perhaps the laser system senses the resistance or just activates the function on a predetermined schedule.

Lydall Chiller

In this section, the flow switch is visible in the lower left corner. Towards the top are the capped refrigerant fill and evacuation ports on the low and high side. A pressure sensor is also visible (orange and yellow wires). A refrigerant sight glass is provided to monitor refrigerant flow and also includes a chemical moisture indicator. The indicator in this chiller appears to be purple, which means caution based on the key on the sight glass. Perhaps the refrigerant circuit has accumulated a bit of moisture. Luckily, the chiller works fine and this has not been an issue as of yet.

Lydall Chiller

This section includes some relays and a contactor responsible for switching the high-current components such as the compressor, fan, and pump. The relays are commanded by the digital controller. The transformer labeled CT1 is the control transformer that steps down the 240 VAC input to around 24V for use by the low-voltage control electronics. This is further rectified and reduced on the digital board.

Lydall Chiller

This is the Lydall Chiller Board (REV 1.3 / 2005). This serves as the chiller's full-authority digital control and monitoring system. It's based around a Microchip PIC18LF6720 8-bit MCU which constantly monitors all inputs and sensors and subsequently controls the chiller via a series of relay outputs. Once powered, the chiller is started by the REMOTE input. Supplying around 7V DC equates to a chiller run request and will start the chiller and pump. It will continue to run as long as no faults are detected and power to the REMOTE input is maintained. The status of the chiller can be monitored over RS-485 by a proprietary protocol that we decoded (more information provided further down on this page). The temperature setpoint can also be adjusted over the RS-485 interface. The chiller stores the setpoint and does not require any input over RS-485 to run. Rather than simply cycling the compressor on and off, it appears to maintain the setpoint with a PID loop that drives the SSR output, while the LEVEL 1 relay switches a large solenoid valve in the main cooling loop whenever cooling is called for. We originally assumed the small resistive heater was used to fine-tune the setpoint, but that is now in question (see below). The logic contained within the firmware of this board is capable of protecting the system from damage in the event of faults such as insufficient flow, low reservoir level, high or low refrigerant pressure, loop temperature limits (below 4 °C or above 40 °C), and RTD sensor failure. After digging through the firmware, we found no anti-short-cycle timer for the compressor, so it does not appear to protect the system from short-cycling. The only start delay is a 10 second window after startup where a low flow fault is ignored, giving the pump time to establish flow. When we first worked with this chiller, it powered on briefly and then shut down. It refused to run for any subsequent attempts. After checking the coolant reservoir and status LEDs, we determined that it was low on water. Adding water and then restarting it solved this problem immediately and allowed the chiller to run without issues.

Lydall Chiller

This is a small additional board mounted to the side of the electronics tray. It's labeled "pump inrush board" and appears to serve that exact function. This helps prevent disruptions to the electronics and other components from the large inrush current when the pump starts.

Lydall Chiller

We're not entirely sure of the purpose of this board, but it includes a relay, connections to the main chiller board, LM324 operational amplifier, voltage regulator, and the connection for the status LED. It may just be a simple status monitoring board. A bi-color LED is connected to a 2-pin header on this board and can be used to quickly tell whether the system is powered on and if the compressor is currently running. Green indicates compressor not running, but loop temperature within range. Red indicates loop temperature not within range. During bench testing, we noticed that the PHASE LED on the chiller board lights up together with the red status LED and turns off when it goes green. So on this unit, that signal appears to act as a call for cooling rather than a phase monitor.

Lydall Chiller

The electronics tray can be removed from the top of the chiller after undoing four nuts with lock washers, two of which are directly beside the control transformer. The usage of electrical connectors allows the chiller electronics to be swapped out without having to disassemble the entire unit.

Lydall Chiller

Here are the majority of the connections from the control and power distribution tray that lead to all the individual sensors and devices within the chiller. The drain line (blue hose with silver CPC fitting) is also visible. The usage of quick-disconnect fittings and electrical plugs makes this a very serviceable unit.

Lydall Chiller

Here is a view of the top of the chiller with the control electronics tray removed and placed off to the side. The water reservoir is visible on the left with a green hose coming from the top. This is for the external fill port. To the right of the reservoir is the pump and VFD. Common chiller components such as the compressor and coolant lines are visible above the reservoir and pump. Specific sections of the copper coolant lines are wrapped in a sticky insulating material to prevent condensation buildup.

Lydall Chiller

This side view of the Fluid-o-Tech TMFE1 VFD shows the fins for heat dissipation and DIP switches for configuration. As presently configured, this VFD will spin the pump at around 1750-2000 RPM without any external control or monitoring. We are basing this off the TMFR2/TMFE2 manual as we were unable to locate the exact manual for this pump/driver combination. Assuming the DIP switch configuration is the same across models, it should be around 1750-2000 RPM.

Lydall Chiller

RS-485 Communication

Communicating with this chiller was a learning experience. Luckily, the system designed to control and monitor it (AMS Greenlight HPS) was in working condition, so we captured and analyzed the RS-485 communication between the laser control system and the chiller control board. From startup to shutdown, the laser polls the chiller board but does not attempt to write or adjust any parameters. It only reads a variety of status registers. The chiller board is a slave and will not transmit any data unless polled by a master. We wrote a Python program, Lydall Live Monitor [DES-W-1003], that monitors the chiller over RS-485 using an RS-485 to USB adapter. The program can operate in passive mode to listen in on the conversation between the laser controller and the chiller board. The program can also operate in active mode to poll a standalone chiller being operated outside of the context of the original laser system. We don't recommend polling the chiller while the laser controller is also polling it, as this could cause issues.

Important: bias resistors are needed to pull the RS-485 A and B channels up and down respectively. We had success using 1,000 ohm resistors to pull RS-485 A up to ~3.6V DC and B down to signal ground. Monitoring the chiller without the laser control board connected (using the script in active mode) may not work properly until the bus is properly biased. Based on our testing, termination resistors are not necessary for short links.

A screenshot of the chiller live monitoring program is provided below. It's very basic and only intended to display the essentials.

Lydall Live Monitor

The serial parameters are: 38400 baud, 8 data bits, no parity, 1 stop bit. Half-duplex RS-485. Below is the poll/reply frame syntax. Every byte in the frame, including the checksum, sums to 0x00 mod 256. To validate any received frame, sum all bytes. The low byte must be 00.

Below is the complete list of commands the chiller firmware accepts, with the checksums included. All of them are read-only register requests except J, which writes the configuration block (PID tuning and setpoint) and saves it to the PIC's internal EEPROM. The laser itself never sends J. Every H value is a signed 32-bit integer equal to the value × 1000, in degrees Celsius where it is a temperature (e.g. H0 = 26100 means a 26.1 °C / 79 °F setpoint). Unknown commands, or a wrong second character, are answered with a NAK (15 00 EB). Frames with a bad checksum get no reply.

Hex Data (send) Register Response
40 42 30 02 43 30 D9 C0 Opto input bitfield (debounced). A bit is set when an input differs from its normal state: for the safety switches (bits 0-4) a set bit means the board LED is dark (alarm), for the others it means the LED is lit. Bit 0 FLOW (set = no flow, normal at idle), bit 1 LEVEL low, bit 2 OVLOAD alarm, bit 3 HI PRES trip, bit 4 LO PRES trip, bit 5 PHASE lit (cooling call, status LED red, drives LEVEL 1), bit 6 SET, bit 7 RUN, bit 8 REMOTE, bit 9 SPARE. Typical run: 0x120 / 0x320
40 42 30 02 42 31 D9 B1 Fault word (0 = healthy). 0x001 low flow (ignored for 10 s after start), 0x002 low level, 0x008 high pressure, 0x010 low pressure, 0x040 loop below 4 °C, 0x080 loop above 40 °C, 0x100 RTD read failure. Faults stop the chiller and stay latched until REMOTE is removed (the RTD fault clears by itself)
40 42 30 02 42 30 DA B0 Stored-data health. 0x01 = RTD calibration CRC bad, 0x02 = PID/config block CRC bad (chiller will not run). 0 = healthy
40 42 30 02 41 30 DB A0 Firmware ID word, constant 0x158 (344)
40 42 30 02 48 30 D4 H0 Temperature setpoint, °C × 1000
40 42 30 02 48 31 D3 H1 Process (loop) temperature, °C × 1000 (live PV)
40 42 30 02 48 32 D2 H2 PID output, % × 1000 (0-100 %). Time-proportions the SSR over a 5 s window
40 42 30 02 48 33 D1 H3 PID proportional term × 1000
40 42 30 02 48 34 D0 H4 PID integral term × 1000
40 42 30 02 48 35 CF H5 PID derivative term × 1000
40 42 30 02 48 36 CE H6 Temperature error (PV - setpoint), °C × 1000
40 42 30 02 48 37 CD H7 PID integral accumulator × 1000
40 42 30 02 48 38 CC H8 Change in error since the last PID update × 1000
40 42 30 01 59 F4 Y H0 through H8 in a single 36-byte reply
40 42 30 01 49 04 I 16-byte configuration block (8 big-endian words): proportional band, integral time, derivative time, (unused), PV filter, PV gain trim %, PV offset trim, setpoint × 10. Example reply 00 50 00 04 00 02 00 00 00 00 FF FC 00 00 01 05 = 26.1 °C setpoint
40 42 30 11 4A 00 50 00 04 00 02 00 00 00 00 FF FC 00 00 01 05 9C J (write) Writes the configuration block (same layout as I) and saves it to EEPROM; the reply is 06 00 FA. This example rewrites the current values (26.1 °C). To change the setpoint, read I, replace the last word with °C × 10, and recalculate the checksum. The firmware does no range checking
40 42 30 01 5A F3 Z Keepalive (bare acknowledge 06 00 FA)

We also wrote a second Python program, Lydall Set Setpoint [DES-W-1003-01], that handles setpoint changes for you. It reads the configuration block with I, changes only the setpoint, writes the block back with J, and then reads it back to verify. It refuses setpoints outside of 10-35 °C, and it won't write anything unless you specifically tell it to. As always, disconnect the laser from the bus first.

Be careful with the J command. The firmware does no range checking whatsoever, so it will happily accept a setpoint low enough to latch a low temperature fault, or PID values that make no sense. Every J command writes to the PIC's EEPROM, so don't send it in a loop. Always read the full block with I first and write the whole thing back with only the setpoint changed, since J also sets the PID tuning and temperature trim values. Also keep in mind that the laser reads the setpoint and loop temperature, so a different setpoint may cause the laser to complain about the chiller even if the chiller itself is perfectly happy.

Status LEDs and I/O

The chiller board has a variety of green status LEDs that are somewhat useful for monitoring the chiller manually. We say somewhat because the silkscreen labels are ambiguous for some of the LEDs. Monitoring the LED behavior as the chiller starts up, runs, and cycles does provide useful insight, but still leaves some unanswered questions. Here is a table of the LEDs along with a description based on our observations and reverse engineering efforts.

Lydall Chiller LEDs
LED Silkscreen Marking I/O Description Firmware signal
+24V - 24V power OK Hardware
VCC - Processor low-voltage DC power OK Hardware
HB - Processor heartbeat (1 s on / 1 s off) RE3, toggled every 1000 ticks of the 1 ms timer (24.576 MHz clock)
SSR O Solid state relay status. On for the PID output fraction (H2) of each 5 s window, about 10 % during a normal run (bench-verified). Its on-time rises as the loop warms, so what the SSR switches still needs confirming (heater suspected) RF6, active-high: SSR on for H2 % of each 5 s window
TEMP (D19) O Never active during normal operation Probably RF5 "Temp Alarm" relay, which this firmware never energizes (no temperature alarm output)
MAIN O Main contactor. On while running: REMOTE present, no fault latched in B1, and valid PID settings RF3 "Main Contactor"
REMOTE I Remote run input status (illuminated when remote run is active). The only way to start or stop the chiller; there is no serial run command RG3 "Remote Run Input", C0 bit 8 (0x100), 1 s debounce
FLOW (D10) O Turns off when SPARE is asserted (observed, matches firmware). Likely the D.I. polishing solenoid output (to be verified) RF1 "Flow Alarm" relay = NOT C0 bit 9
LEVEL 1 O Drives a large solenoid valve in the main cooling loop. On when the PHASE input is lit (status LED red) and REMOTE is present RF0 "Level Fault" relay = C0 bit 5 (PHASE) AND REMOTE; holds its last state while REMOTE is off
TEMP (D2) O Unknown, normally off Probably RF2 "Level Alarm" relay (on when the OVLOAD input alarms, latched until REMOTE is removed); a warning only
SPARE I SPARE input status, laser controller periodically drives the input (likely call for de-ionize filter polishing) RG0 (firmware label "50/60Hz Input"), C0 bit 9 (0x200)
SET I Never active during normal operation. Read and reported only; not used to change the setpoint (that is done with the J command) RD0 "Set Input", C0 bit 6 (0x040)
RUN I Never active during normal operation. Read and reported only RD1 "Run Input", C0 bit 7 (0x080)
OVLOAD I Pump overload, illuminated = normal. Note: this input does not shut the chiller down in this firmware RD2 (firmware label "Level Alarm Input"), C0 bit 2, set when the LED is dark. Mapped by elimination; in a low-water capture it alarmed together with LEVEL, so it may be a second level switch. Drives TEMP (D2); no shutdown
PHASE I Lit together with the red status LED, dark when it turns green (bench-observed). Acts as a cooling call that drives LEVEL 1 (large solenoid); not a phase monitor on this unit RD3 (firmware label "Pump Overload Input"), C0 bit 5, set when the LED is lit
LO PRES I Low pressure switch status, illuminated = normal. Trip stops the chiller RD4 "Low Pressure Input", C0 bit 4, fault B1 0x010
HI PRES I High pressure switch status, illuminated = normal. Trip stops the chiller RD5 "High Pressure Input", C0 bit 3, fault B1 0x008
LEVEL I Level sensor, illuminated during normal operation. Low level stops the chiller RD6 "Level Fault Input", C0 bit 1, fault B1 0x002
FLOW I Flow sensor/switch status, illuminated during normal operation. No flow stops the chiller after a 10 s start-up grace period RD7 "Flow Alarm Input", C0 bit 0, fault B1 0x001

Extracting the code from the PIC microcontroller

We took this reverse engineering exercise a step further by obtaining a PICkit 3 to connect to the chiller board's ISP connector and extract the program code from the chip. The 5-pin connector labeled J9 is a dedicated ISP connector, conveniently populated and even labeled! Manually probing these connections and tracing them back to pins on the PIC MCU confirmed that it had all the necessary connections for ISP (in-system programming). The pin-out for the connector has been provided below. Pins are ordered from left to right, with the locking tab on the bottom.

We were banking on the code protection bits not being set. When set, this function prevents reading of firmware and EEPROM code with debugging tools, as a method to prevent reverse engineering and protect intellectual property. If a chip has these protections enabled, you can only disable them by erasing the chip (useless when reverse engineering) or by following microcontroller exploit techniques. Travis Goodspeed wrote a great book called "Microcontroller Exploits" which covers this topic in detail. Luckily, the only protected section of the PIC microcontroller on this board was the boot block. It's not completely clear why this small (and arguably insignificant) section is protected, while other sections such as the main program memory are not. However, we're not complaining! This specific PIC-18 has 5 sections of program memory, the boot block and blocks 0-3. As mentioned, the boot block was protected on this chip, while program memory blocks 0-3 were unprotected. This allowed us to easily dump all program memory from blocks 0-3. The boot block is so small and only contains boot-related code and vectors, so it's not a big deal for that to be omitted. If you'd like to examine the program code for yourself, you can download the raw hex file at the link below. Keep in mind the first section (0x0000-0x01FF) is blank due to the boot block code protection.

Using a combination of AI-based decompilation tools and Ghidra, we ripped apart the program stored on the PIC. The most notable finding is the presence of a second serial interface, specifically for diagnostic purposes. According to the decompilation, this interface prints human-readable ASCII text and can be used to view the chiller's status, read sensors and inputs, and actuate relays. It appears to use a baud rate of 115200, and typing "U" shortly after startup will cause the system to enter the bootloader. The following functions are listed on the top-level menu of the diagnostic interface: Test Relay Outputs, Test Opto Inputs, Read RTD Input, Test Buzzer, Test SSR Output, Cal RTD Input, Load Default PID, Test FRAM, Current Test, Remote Input DB/Filt Test, Quit. We presume that this is the purpose of the 4-pin header labeled J10 / DEBUG. After further analysis, we're fairly confident this diagnostic menu is not reachable. The code for it is compiled into the firmware, but nothing in the program ever calls it, so it will not respond to commands. Presumably the menu was disabled for the production build and the code was simply left in place. The interface is still used for output, printing a boot banner (FW version 00.00.0158), messages as it loads the PID and calibration data, and "Storing PID gains" every time a J command is received. Enabling the menu would require patching the firmware. If you connect to this port, be careful not to type "U" during the first second or so after power-up, or the chiller will sit in its bootloader instead of running.

Program decompilation also showed us that the cooling loop temperature is sensed by an RTD (resistance temperature detector) and digitized by an LTC2422, which is located near the RTD connector on the chiller board. The formula for this measurement is R = (104857600/raw) - 100. This is also how we learned about the PID-controlled SSR output, driven by the SSR/TEMP connections on the board, which we originally assumed was driving the heater. However, bench testing showed that the SSR is on for the same percentage of time as the PID output (H2), about 10% during a normal run, and its on-time increases as the loop gets warmer. A heater wired this way would add heat when the water is already too warm, which makes no sense. So either the SSR drives something on the cooling side, or the heater is wired so that SSR on means heater off. We'll update this page once we confirm what the SSR actually switches. Additionally, we used this information to better correlate the inputs and LEDs to their true functions. Lastly, there is an external FRAM chip located adjacent to the PIC microcontroller, and the program code set up communication with it. However, the RTD calibration and the configuration block (PID tuning and setpoint) are stored on the PIC MCU's internal EEPROM, not the FRAM. The configuration block is stored twice, and each copy is protected by a CRC. If both copies fail the check, the chiller refuses to run rather than falling back to the factory default setpoint of 25.0 °C.

Below are some useful resources for learning about chillers in general. There is no public documentation for this model of chiller so we included as much relevant information as possible, but most applies to different variations/models. Lastly, the Python programs for monitoring this chiller and changing its setpoint over RS-485 can be downloaded at the links below.